India has four seismic zones, II to V, under IS 1893 (Part 1):2016. How to find your city's zone, and what each zone changes in a building's design.
India has four seismic zones under IS 1893 (Part 1):2016, the Bureau of Indian Standards (BIS) code for earthquake-resistant design. They are zones II, III, IV and V, and zone V expects the strongest shaking. The zone your site falls in sets the earthquake force your building is designed for and the detailing rules it has to follow.
What are the seismic zones of India?
The zone map is based on the intensity of shaking recorded in past earthquakes, together with known epicentres and the geology of each region. Each zone is broadly linked to a level on the MSK intensity scale. There is no longer a zone I, so zone II is now the lowest.
About 59 per cent of India’s land area lies in zones III, IV and V.
| Zone | Zone factor (Z) | Associated intensity (MSK) | Towns in this zone (Annex E) |
|---|---|---|---|
| II | 0.10 | VI or less | Bengaluru, Hyderabad, Jaipur, Nagpur |
| III | 0.16 | VII | Mumbai, Chennai, Kolkata, Ahmedabad, Kochi |
| IV | 0.24 | VIII | Delhi, Chandigarh, Dehradun, Patna |
| V | 0.36 | IX and above | Guwahati, Srinagar, Shillong, Bhuj |
Is there a new seismic zone map of India?
In late 2025, BIS released a revised code, IS 1893 (Part 1):2025, with a new zone map. Press reports described these changes:
- A new zone VI, the highest category, covering almost all of the Himalayan arc.
- A map based on probabilistic seismic hazard assessment.
- About 61 per cent of India’s land area in moderate to high hazard zones.
- Provisions for non-structural items such as parapets, overhead tanks and lifts.
The revised zonation was withdrawn in March 2026. On 1 April 2026, the Ministry of Earth Sciences told the Lok Sabha that the zone map in IS 1893 (Part 1):2016 remains the current standard.
We design to IS 1893 (Part 1):2016, which is the current BIS edition. If BIS publishes a new edition, we will design to that.
How do I find the seismic zone of my city?
- Check the town list. Annex E of IS 1893 (Part 1):2016 gives the zone and zone factor for many towns with more than 3 lakh people (Census 2011).
- Check the map. For smaller towns and villages, use the zone map in the code, or the state earthquake hazard maps in the Vulnerability Atlas of India, published by the Building Materials and Technology Promotion Council (BMTPC). The atlas maps show district boundaries.
- Use the higher zone at a boundary. The code says towns on the line between two zones are treated as being in the higher zone.
- Ask your engineer. The structural design should state the zone and zone factor it uses.
What does each zone mean for building design?
The zone factor feeds directly into the design earthquake force. With everything else equal, a building in zone V is designed for 3.6 times the force of the same building in zone II.
What the building is used for also matters. The code gives schools, hospitals and large halls where people gather an importance factor of 1.5, which raises the design force by half. Residential and commercial buildings with more than 200 occupants get 1.2.
- Zone II. Every building still needs earthquake design to IS 1893. Ductile detailing to IS 13920 is optional. Load-bearing masonry needs a concrete band at lintel level under IS 4326, and one at roof level unless a concrete roof slab does that job.
- Zone III. Concrete and steel buildings must be designed to be ductile, and IS 13920 detailing is mandatory for the concrete frames and walls that resist earthquake forces. Some irregular layouts are not allowed, and others need a dynamic analysis.
- Zones IV and V. The zone III rules apply, and more are added. Vertical shaking has to be considered. Separate footings must be tied together unless they rest on rock. Load-bearing masonry needs vertical steel bars at corners and wall junctions. In zone V, IS 4326 limits such buildings to three storeys.
Earthquake-resistant building design: common weak points
These features have performed badly in past earthquakes. Each can be designed for, and most are easiest to deal with while the plan is still being drawn.
- Open ground storey. Stilt parking under walled floors leaves a soft, weak storey at the bottom. In the 2001 Bhuj earthquake, more than a hundred such buildings collapsed in Ahmedabad, about 225 km from the epicentre. IS 1893 asks for concrete walls or bracing in selected bays to restore stiffness and strength.
- Short columns. Columns on sloping ground, beside part-height walls at windows, or under a loft slab are stiffer than their neighbours. They attract more force and can fail in shear.
- Floating columns. A column that starts on a beam concentrates damage. The code says such columns should not form part of the earthquake-resisting system.
- Heavy water tanks on the roof. The earthquake force on each floor grows with its weight and its height above the ground. A large tank adds weight at the highest level, so it has to be in the structural design, along with its supports.
- Masonry without bands. Walls that are not tied together can fall outwards. Continuous concrete bands at lintel and roof level hold them together.
- Poorly tied columns. Ties at column ends need close spacing and 135 degree hooks, as IS 13920 requires.
Worked example: Kerala in zone III
Almost all of Kerala is in zone III. Kochi, Kozhikode and Thiruvananthapuram are all listed with a zone factor of 0.16. BMTPC’s hazard map for Kerala shows only a narrow strip of hill country, along part of the eastern border, in zone II.
The state has a record of moderate earthquakes. Kerala’s State Disaster Management Plan counts about 60 recorded earthquakes, historical and recent. It names a magnitude 5.0 earthquake near Erattupetta on 12 December 2000 as the major event of the preceding 20 years, and reports no major deaths or damage from earthquakes in recent times.
For buildings in Kerala, zone III means:
- A reinforced concrete house, apartment block, school or place of worship is detailed to IS 13920.
- A one or two storey load-bearing masonry house needs a lintel band, and a roof band unless a concrete slab does that job. At three or four storeys, it also needs vertical steel at corners, junctions and door and window jambs.
- A load-bearing masonry school needs that vertical steel even at one or two storeys, because of its higher importance factor.
- Houses on hill slopes need their stepped columns designed for the short column effect.
We cover ground, floods and slopes alongside earthquakes in engineering for India’s conditions.
When should you involve a structural engineer?
Most of the weak points above are settled when the plan is drawn, before a column is cast. Bring in a structural engineer:
- before the architectural plan is fixed, so columns, walls and parking work for earthquake loads;
- on sloping, filled or soft ground, or where loose, waterlogged sand could liquefy;
- for schools, hospitals and halls where many people gather;
- before adding a floor or a large water tank, or opening up a ground floor for parking or shops;
- to assess an older building designed before the current codes.
We design every building for earthquake forces to IS 1893 and detail its reinforced concrete to IS 13920. See our structural engineering service, or start a project to tell us about your building.
Sources
- Ministry of Earth Sciences, Lok Sabha reply, 1 April 2026 (PIB): the 2016 zone map remains the standard; revised zonation withdrawn in March 2026.
- IS 1893 (Part 1):2016 (BIS text, public copy): zones, zone factors, intensities, town list, boundary rule, importance factors and design rules by zone.
- IS 13920:2016 (BIS text, public copy): ductile detailing mandatory in zones III to V, optional in zone II.
- IS 4326:2013 (BIS text, public copy): masonry categories, bands, vertical steel and the zone V storey limit.
- ThePrint, 2 December 2025: changes in the 2025 map; land share by zone under the earlier map.
- IIT Kanpur and BMTPC, Earthquake Tip 21: open ground storeys and the Ahmedabad collapses of 2001.
- BMTPC Vulnerability Atlas, Kerala earthquake hazard map: Kerala’s zones; maps for other states are on the same site.
- Kerala State Disaster Management Plan 2016 (KSDMA): Kerala in zone III and its earthquake history, including 12 December 2000.
Common questions
Which seismic zone is my city in?
Look up your town in Annex E of IS 1893 (Part 1):2016, which lists the zone of many towns with more than 3 lakh people, or check your state's map in the BMTPC Vulnerability Atlas. If your site sits on a zone boundary, use the higher zone.
Does India have a seismic zone VI?
Not at present. A 2025 revision introduced a zone VI for the Himalayan arc, and that zonation was withdrawn in March 2026. The four-zone map of 2016 remains the standard.
Is an earthquake-resistant building earthquake-proof?
No. A building designed to the Indian codes can be damaged in strong shaking. The aim of the design is that it does not collapse.
Can an older building be made safer against earthquakes?
Often, yes. A structural engineer can assess it against the current codes and design strengthening, such as adding concrete walls to an open ground storey.